Few indoor climate topics are quoted as often, or as loosely, as the link between CO2 and how well people think. The same studies appear online with contradicting numbers, and a "1,000 ppm limit" is attributed to a standard that no longer contains it. This page sets out what the original research and the main building rules actually say, with a link to each source.
Office workers did simulated office work in a controlled environment on different days, with CO2 set at around 550, 945 and 1,400 ppm. Compared with the 550 ppm baseline, cognitive scores were on average 15% lower at 945 ppm and 50% lower at 1,400 ppm. Published in Environmental Health Perspectives. Original paper and summary by Lawrence Berkeley National Laboratory
22 participants made decisions in a chamber at 600, 1,000 and 2,500 ppm, with CO2 added so that nothing else in the air changed. At 1,000 ppm, performance was moderately and significantly lower on six of nine decision-making scales. At 2,500 ppm, seven of nine scales dropped sharply, some to levels the test rates as dysfunctional; the "initiative" score, for example, fell from 20.1 to 1.4. Original paper, Environmental Health Perspectives
302 office workers in six countries were followed in their real offices. For every 500 ppm increase in CO2, response times were 1.4 to 1.8% slower and correct answers per minute fell by 2.1 to 2.4%. The researchers found no level below which CO2 and fine particles had no effect. Original paper, Environmental Research Letters
A statistical analysis of many studies found that office work performance rises by about 0.8% for every 10 cfm (4.7 l/s) per person of extra ventilation, for starting rates between 6.5 and 14 l/s per person, with smaller gains above that. Summary by Lawrence Berkeley National Laboratory
The report "Health, Wellbeing and Productivity in Offices" concludes from the research it reviewed that better indoor air quality can improve productivity by 8 to 11%. WorldGBC
The studies agree on direction more than on exact numbers: rooms that fill up without enough fresh air make people slower and less sharp, and meeting rooms get there fastest. Continuous CO2 and occupancy measurement per room shows where and when that happens, so ventilation can follow real use instead of a fixed schedule, which also saves energy in rooms that stand empty. Read how space and indoor climate data work together.
Last reviewed September 2026. If you spot a newer study or an error, tell us and we will update this page.